SIMATIC S7-1200, Analog Input SM 1231 RTD
Module Type: 4x AI RTD (Resistance Thermometer)
Product type: SM 1231, AI 4x16 bit RTD
Technical unit: °C / °F (adjustable)
Rated value (DC): 24 V
Current consumption:
Typical: 40 mA
From backplane bus 5 V DC: typ. 80 mA
Power loss: typ. 1.5 W
Number of inputs: 4 (Resistance Thermometer)
Permissible input voltage: ±35 V
Input ranges (Resistance Thermometer):
Pt types: Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000
Ni types: Ni100, Ni120, Ni200, Ni500, Ni1000
Cu types: Cu10, Cu50, Cu100
LG-Ni1000
Resistors: 150 Ω, 300 Ω, 600 Ω
Input resistance examples:
Cu10: 10 Ω
Pt100: 100 Ω
Ni1000: 1,000 Ω
Pt500: 500 Ω
Voltage / Current / Thermocouple: Not supported
Measurement principle: Integrating
Resolution (with overrange): 15 bit + sign
Integration time: Not parameterizable
Interference voltage suppression: 85 dB at 50 / 60 / 400 Hz
Repeat accuracy at 25 °C: ±0.05%
Temperature error: ±0.1% at 25 °C, ±0.2% up to 55 °C
Common mode interference: min. 120 dB
Alarms / Diagnostics function: Yes, can be read out
Monitoring: Supply voltage and wire-break
LED indicators: Status of inputs, maintenance
IP rating: IP20
Ambient temperature (operation): -20 °C to 60 °C
Horizontal installation: -20 °C to 60 °C
Vertical installation: -20 °C to 50 °C
Storage / transport temperature: -40 °C to 70 °C
Air pressure: 795–1080 hPa (operation), 660–1080 hPa (storage)
Relative humidity: Max. 95% at 25 °C, no condensation
Pollutant concentrations: SO2 < 0.5 ppm, H2S < 0.1 ppm
Enclosure material: Plastic
Dimensions: W 45 mm × H 100 mm × D 75 mm
Weight: Approx. 220 g
| Specification | Details |
|---|---|
| Product Name / Model | 6ES7231-5PD32-0XB0 |
| Voltage | 24 V DC |
| Input current | 40 mA |
| Power loss | 1.5 W |
| IP protection | IP20 |
| Humidity | 95 % |
| Operation temperature | -20 - +60 Degree C |
| Dimensions | 45 x 100 x 75 mm |
| Net weight | 220 g |



Price: Â