Article No.: 6EP1334-3BA10
SITOP PSU200M 10 A stabilized power supply
Input: 120/230500 V AC
Output: 24 V DC / 10 A
Type of power supply network: 1-phase and 2-phase AC
Supply voltage at AC: Set by selector switch on the device
Supply voltage 1 at AC: 120 ... 230 V
Supply voltage 2 at AC: 230 ... 500 V
Input voltage 1 at AC: 85 ... 264 V
Input voltage 2 at AC: 176 ... 550 V
Wide range input: Yes
Overvoltage overload capability: 1300 Vpeak, 1.3 ms
Buffering time for rated output current in case of power failure, min.: 25 ms
Operating condition of mains buffering:
Vin = 120/230 V, typ. 150 ms
Vin = 400 V
Line frequency: 50/60 Hz
Line frequency range: 47 ... 63 Hz
At rated input voltage 120 V: 4.4 A
At rated input voltage 230 V: 2.4 A
At rated input voltage 500 V: 1.1 A
Current limitation of inrush current at 25 C, max.: 35 A
It value, max.: 4 As
Type T 6.3 A (not accessible)
Recommended miniature circuit breaker:
1-phase operation: from 6 A (10 A) characteristic C (B)
2-phase operation: 2-pole or circuit breaker 3RV2011-1EA10 (setting 3.8 A) or 3RV2711-1ED10 (UL 489) at 230 V; 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489) at 400/500 V
Voltage curve: Controlled, isolated DC voltage
Output voltage at DC rated value: 24 V
Output voltage adjustable: Yes; via potentiometer
Adjustable output voltage: 24 ... 28.8 V
Relative overall tolerance of voltage: 3 %
Relative control precision of output voltage:
On slow fluctuation of input voltage: 0.1 %
On slow fluctuation of ohm loading: 0.1 %
Residual ripple, max.: 50 mV
Voltage peak, max.: 200 mV
Display for normal operation: Green LED for 24 V OK
Type of signal at output relay contact: Normally open, contact rating 30 V DC / 0.1 A
Behavior of output voltage when switching on: Overshoot of Vout approx. 3 %
Response delay, max.: 1 s
Voltage increase time, typical: 50 ms
Rated value: 10 A
Rated range: 0 ... 10 A; +60 ... +70 C: Derating 2 %/K (120 V, 230 V) or 3.5 %/K (400 V)
Supplied active power, typical: 240 W
Short-term overload current: 30 A
Duration of overloading capability: 25 ms
Constant overload current: 12 A
Bridging of equipment: Yes; switchable characteristic
Number of parallel-switched equipment for increasing power: 2
Efficiency: 91 %
Power loss, typical at rated output voltage & current: 24 W
Power loss, max during no-load operation: 6 W
Relative control precision of output voltage with rapid input fluctuation 15 %, typical: 0.1 %
Relative control precision of output voltage for load step 50/100/50 %, typical: 3 %
Setting time:
Load step 50 100 %: 2 ms (typical)
Load step 100 50 %: 2 ms (typical)
Maximum: 5 ms
Overvoltage protection: < 35 V
Output short-circuit proof: Yes
Short-circuit protection: Constant current approx. 12 A or latching shutdown
Enduring short-circuit current RMS, typical: 12 A
Display for overload/short-circuit: LED yellow "overload", LED red "latching shutdown"
Galvanic isolation between input and output: Yes
Safety extra-low output voltage Uout: acc. to EN 60950-1 and EN 50178
Operating resource protection class: Class I
Leakage current, max.: 3.5 mA; typical: 0.32 mA
Protection class: IP20
Emitted interference: EN 55022 Class B
Mains harmonics limitation: EN 61000-3-2
Interference immunity: EN 61000-6-2
CE marking: Yes
UL approval: Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
CSA approval: Yes; cULus-Listed, File E197259
UKCA marking: Yes
EAC approval: Yes
Regulatory Compliance Mark (RCM): Yes
NEC Class 2: No
SEMI F47: Yes
CB-certificate: Yes
MTBF at 40 C: 1 055 408 h
IECEx: No
ATEX: No
ULhazloc: No
cCSAus Class 1 Division 2: No
FM registration: No
Shipbuilding approval: Yes
American Bureau of Shipping Europe Ltd. (ABS): Yes
French marine classification society (BV): No
Det Norske Veritas (DNV): Yes
Lloyds Register of Shipping (LRS): No
Environmental Product Declaration: Yes
Global warming potential (CO2 eq):
Total: 763.9 kg
During manufacturing: 12.6 kg
During operation: 751 kg
After end of life: 0.18 kg
Operation: -25 ... +70 C; startup tested from -40 C nominal voltage
Transport: -40 ... +85 C
Storage: -40 ... +85 C
Environmental category IEC 60721: Climate class 3K3, 5 ... 95 % no condensation
Type: Screw terminal
Input L, N, PE: 1 screw terminal each, 0.2 ... 2.5 mm
Output +, -: 2 screw terminals each, 0.2 ... 2.5 mm
Auxiliary contacts 13, 14 (alarm): 1 screw terminal each, 0.14 ... 1.5 mm
Width Height Depth of enclosure: 70 125 121 mm
Installation width mounting height: 70 225 mm
Required spacing: Top 50 mm, Bottom 50 mm, Left 0 mm, Right 0 mm
Fastening method: Snaps onto DIN rail EN 60715 35x7.5/15
DIN-rail mounting: Yes
S7 rail mounting: No
Wall mounting: No
Housing can be lined up: Yes
Net weight: 0.8 kg
| Specification | Details |
|---|---|
| Product Name / Model | 6EP1334-3BA10 |
| Voltage | 120 - 230 V |
| Input voltage | 85 - 264 V |
| Phases | 1-phase and 2-phase AC |
| Frequency | 50/60 Hz |
| IP protection | IP20 |
| Efficiency | 91 % |
| Operating Temperature | -25 - +70 Degree C |
| Cooling | Self-cooled |
| Net weight | 0.8 kg |
| Dimensions | 70 x 125 x 121 mm |




Price:
Price 10478 INR / Piece
Minimum Order Quantity : 1 Piece
Protection Level : Other, IP20
Color : Black
Mounting Type : DINrail mounting
Frequency (MHz) : 4763 Hertz (HZ)
Price 10478 INR / Piece
Minimum Order Quantity : 1 Piece
Protection Level : Other, IP20
Color : Black
Mounting Type : DINrail mounting
Frequency (MHz) : 4763 Hertz (HZ)
Price 10478 INR / Piece
Minimum Order Quantity : 1 Piece
Protection Level : Other, IP20
Color : Grey
Mounting Type : DINrail mounting
Frequency (MHz) : 4763 Hertz (HZ)
Price 10478 INR / Piece
Minimum Order Quantity : 1 Piece
Protection Level : IP65
Color : Grey
Mounting Type : Panel Mount
Frequency (MHz) : 50/60 Hertz (HZ)