Product Type: DQ 8x230 V AC / 5 A ST (Relay)
HW Functional Status: FS02
Firmware Version: V2.1.0 (FW update possible)
Channels: 8, in groups of 1
Diagnostics: Yes (Substitute value: switching cycle counter)
Safety Functions:
Supports safety-oriented shutdown of load groups up to SIL1 (EN IEC 62061:2021)
Category 2 / PL c (EN ISO 13849-1:2015)
Front Connector: To be ordered separately (screw terminals or push-in)
STEP 7 TIA Portal: from V12
STEP 7: from V5.5 SP3
PROFIBUS GSD Version: V1.0 / V5.1
PROFINET GSD Version: V2.3
DQ: Yes
MSO (Multiple Signal Output): Yes
Integrated Operating Cycle Counter: Yes (FW V2.1.0 or higher)
Prioritized Startup: Yes
Rated Value: 24 V DC
Permissible Range: 19.228.8 V DC
Reverse Polarity Protection: Yes
Max Current Consumption: 80 mA
Backplane Bus Power Consumption: 0.8 W
Power Loss (typ.): 5 W
Type: Relays
Number of Outputs: 8
Current-Sinking / Sourcing: Yes
Parameterizable: Yes
Short-Circuit Protection: No
Controlling a Digital Input: Yes
Motor Starter Size (NEMA): Max. 5
Switching Capacity:
Lamp load: max. 1,500 W (10,000 cycles)
Low-energy/fluorescent lamps: 10 58 W (25,000 cycles)
Conventional fluorescent: 1 58 W (25,000 cycles)
Uncompensated fluorescent: 10 58 W (25,000 cycles)
Output Current:
Rated: 5 A per channel
Min: 5 mA / 10 V
Max (thermal continuous): 8 A
Residual current for signal "0": 0 A
Parallel Switching:
Logic links: Yes
Redundant control: Yes
Switching Frequency:
Resistive load: 2 Hz
Inductive load: 0.5 Hz
Lamp load: 2 Hz
Total Current:
Per channel: max. 8 A
Per group: max. 8 A
Per module: max. 64 A
Number: 8
Relay Coil Voltage (L+): 24 V DC
Coil Current (typ.): 80 mA
Operating Cycles (max.): 4,000,000
Relay Approval: UL 508 (250 V AC / 5 A g.p., 120 V AC TV-4 tungsten)
Cable Length:
Shielded: max. 1,000 m
Unshielded: max. 600 m
Diagnostics Function: Yes
Substitute Values Connectable: Yes
Alarms: Diagnostic alarm, Maintenance interrupt
Voltage Monitoring: Yes
Wire-break / Short-circuit Detection: No
Status LEDs:
RUN: Green
ERROR: Red
MAINT: Yellow
PWR: Green
Channel Status: Green
Between Channels: Yes (different phases permitted, groups of 1)
Between Channels and Backplane Bus: Yes
Between Channels and Load Voltage L+: Yes
Permissible Potential Difference: 250 V AC (500 V AC for different phases)
Isolation Tested:
Between channels: 3,100 V DC
Channels & backplane bus: 3,100 V DC
Channels & L+: 3,100 V DC
L+ & backplane bus: 707 V DC
Safety Functions: Yes, up to PL c / SIL 1 / Cat. 2
Siemens Eco Profile (SEP): Yes
Global Warming Potential (CO eq):
Total: 43.8 kg
Production: 9.5 kg
Operation: 34.5 kg
End-of-life: -0.231 kg
Approvals: KC, FM, NK, CCS
Horizontal Installation: -30 C to 60 C (From FS03)
Vertical Installation: -30 C to 40 C
Storage / Transport: Not specified
Width: 35 mm
Height: 147 mm
Depth: 129 mm
Weight: ~350 g
| Specification | Details |
|---|---|
| Product Name / Model | 6ES7522-5HF00-0AB0 |
| Voltage | 24 V DC |
| Input current | 80 mA |
| Power | 0.8 W |
| Power loss | 5 W |
| Operation temperature | -30 - +60 Degree C |
| Dimensions | 35 x 147 x 129 mm |
| Net weight | 350 g |

Price:
Price 155885 INR / Piece
Minimum Order Quantity : 1 Piece
Application : Automation
Humidity : N/A
Power Mode : Electric
Frequency : 50/60 Hertz (HZ)
Price 11365 INR / Piece
Minimum Order Quantity : 1 Piece
Application : Automation
Humidity : N/A
Power Mode : Electric
Frequency : 50/60 Hertz (HZ)
Price 9600 INR / Piece
Minimum Order Quantity : 1 Piece
Application : Automation
Humidity : N/A
Power Mode : Electric
Frequency : 50/60 Hertz (HZ)
Price 18850 INR / Piece
Minimum Order Quantity : 1 Piece
Application : Automation
Humidity : 95 %
Power Mode : Electric
Frequency : 5060 Hertz (HZ)